Setting Panic of an electronic pressure switch for a credit card applicatoin in the vacuum range isn’t a self-explanatory task. The next article therefore explains what should be taken into account with this setting. It involves a pressure switch with a hysteresis function. Instruments with this particular configuration are most regularly installed in industrial applications.
Electronic pressure switches, like the WIKA models PSD-4 and PSD-4-ECO or the A-1200 pressure sensor with IO-Link, operate as ?normally closed? or ?normally open?, depending on task. The next graphics illustrate both switching functions with the respective switch and reset points:
In principle, the following applies: The switch point (SP) is higher than the reset point (RP) and the start of measuring range (MRS) is always smaller than the end of measuring range (MRE). This rule could be easily understood with settings for ambient air pressures.
Example: Control of vacuum pressure pump
On the other hand, setting the switch points in the vacuum range and thus, ultimately, the switching function, requires more attention. To illustrate this, let?s take the control of a vacuum pump, for example, which must maintain a vacuum between -0.7 bar and -0.5 bar. For the task described, we select a pressure switch with a measuring range of -1 ? 0 bar.
The start of measuring range (MRS) is therefore -1 bar, the finish of measuring range (MRE) 0 bar. This means: At 0 bar (= start of operation) the switch ought to be closed, so that you can activate the vacuum pump. If the pressure drops to -0.7 bar, the switch must open and prevent the pump. As soon as the pressure reaches the upper limit value of -0.5 bar, the pump should once again start and run before pressure has again dropped to -0.7 bar.
ow must the switch points be set within this vacuum range? Let?s take both pictures and translate MRS and MRE:
Here it really is clear that the ?normally open? function should be selected, otherwise the pump wouldn’t normally activate. After entering the switch points, the schematic is obtained, which shows how the pressure switch functions relative to the example:
Note
Information about WIKA?s electronic pressure switches are available on the WIKA website. Would Last like to buy pressure switches? In our WIKA online-shop you will discover a few of our standard designs. In case you have any questions, your contact will gladly assist you to.
Also read our posts
What is meant by the switching function ?hysteresis? with electronic pressure switches?
What’s the difference between the switching functions ?hysteresis? and ?window? in pressure switches?
What’s meant by the ?normally open? switching function with pressure switches?