How to prevent the ingress of moisture through the cable of submersible pressure transmitters and level probes?

If you need to measure the degree of a liquid easily and reliably, a lot of people will do this using hydrostatic pressure measurement, e.g. with a submersible pressure transmitter or a so called level probe. The characteristic submersed application implicates a maximum contact with the surrounding, mainly water-based medium, respectively to ?moisture?.
Exposure isn’t just limited by the wetted elements of the pressure sensor housing, but also to the entire immersed length of the cable. In addition, beyond your directly immersed level probe parts, the cable, and in particular the cable end, tend to be exposed to moisture due to splash water, rain and condensation. This is true not merely during operation, but even more during installation and commissioning, or when maintenance or retrofitting is necessary. Irrespective of the prospective application, whether in water and wastewater treatment or in tank monitoring, moisture ingress into the cable ends of the submersible pressure transmitter can occur early and irreversibly with insufficient protection measures, and, in virtually all cases, lead to premature failure of the instrument.
The ingress of moisture in to the cable outlet and from there on downwards in to the electronics of the level probe must be actively eliminated by preventive actions by an individual. To measure the level with highest accuracy, the varying ambient pressure above the liquid media, which is also ?resting? on the liquid, should be compensated contrary to the hydrostatic pressure functioning on the pressure sensor (see article: hydrostatic level measurement).
Ventilation tube
Thus, it is logical that there surely is a constant threat of a moisture-related failure because of moisture ingress (both via the ventilation tube and through the actual cable itself) if there are no adequate precautionary measures. To compensate the ambient pressure ?resting? on the media, a ventilation tube runs from the sensor element within the level probe, through the cable and from the level probe by the end of the cable. Because of capillary action within the ventialation tube used for ambient pressure compensation, moisture can also be transported from the encompassing ambience down to the sensor.
Thus not only air, but additionally moisture penetrates in to the tube, hence the sensor in the probe and the electronics around it might be irreparably damaged. This may lead to measurement errors and, in the worst case, even to failure of the particular level probe. To avoid any premature failure, the ingress of moisture into the ventilation tube should be completely prevented. Additional protection against moisture penetration through the ventilation tube is provided by fitting an air-permeable, but water-impermeable filter element at the end of the vent tube.
bare wires
Not to be ignored is also the transport of the liquid through high-humidity loads along the only limitedly protected internals of the cable, e.g. across the wires, completely down to the submersible pressure transmitter. As a respected manufacturer, WIKA uses appropriate structural design to avoid fluid transport, so far as possible, in to the electronics of the submersible pressure transmitter. Because of molecular diffusion and capillary effects, a guaranteed one-hundred percent protection over the full lifetime of the submersible pressure transmitter, however, is never achievable.
It is therefore recommended that the cable is definitely terminated in a waterproof junction box with the correct IP protection (e.g. IP65) which is matched to the installation location. If this cable junction box is exposed to weather and varying temperature conditions, it is also recommended to pay focus on a controlled pressure equalisation as a way to prevent the formation of condensation or perspiration water and pumping effects. To address this technical requirement, as an accessory to a submersible pressure transmitter, it is possible to order a connection box with an integrated air-permeable, water-impermeable membrane.
Ultimately, moisture ingress can happen not merely through the exposed end of the cable, but also through mechanical damage to the cable sheath or due to liquid diffusion due to improper chemical resistance of the cable material. In this article ?Selection criteria for preventing moisture-related failures of submersible pressure transmitters or level probes? this failure mode is described at length.
WIKA offers comprehensive solutions for the hydrostatic-pressure level measurement. For further assistance in selecting the submersible pressure transmitter the most suitable for your application, please use our contact form.
Please find Scarce with this topic on our information platform ?Hydrostatic level measurement?